H.D.S. Indoor Cable

H.D.S. Indoor Cable Cat. 7

H.D.S. Category 7 S/FTP indoor cable for easy cabinet-to-cabinet cabling in data centers and multi-connections from distribution rooms to sub-distribution rooms. The cable structure consists of 24 pair-shielded cable elements, with 4 pairs combined into one stranded element. Each stranded element is marked with a number band for easy identification. The flexible central strain relief element provides excellent protection for the cable during installation. The jacket is made of flexible LSOH material.

6 x (4 x 2 x AWG 23) S-FTP B2ca

Application standards:

  • IEC 61156-5, ISO/IEC 11801 2nd ed.
  • EN 50173-5, EN 50288-4-2

Fire class:

  • B2ca s1,d1,a1 acc. EN 50399, IEC 60332-1, IEC 60754-2, IEC 61034

Technical data:

  • Electrical values Cat.7
  • Conductor AWG 23/1
  • Conductor diameter 1.4 mm
  • Cable diameter 18.2 mm
  • Weight 330 kg/km
  • Cable sheath FR-LSZH
  • Jacket color Aqua, RAL 6027
  • Transmission length Class EA ≤ 90 m
  • Fire load 3,120 MJ/km; 0.87 kWh/m
  • Temperature range -20°C to +60°C
  • Max. pull-in force 840 N
  • Permissible bending radius ≥ 100 mm (at rest), ≥ 200 mm (during pull-in)

 

6 x (4 x 2 x AWG 23) S-FTP Dca

Application standards:

  • IEC 61156-5, ISO/IEC 11801 2nd ed.
  • EN 50173-5, EN 50288-4-2

Fire class:

  • Dca s2,d2,a1 EN 50575:2014 + A1:2016, IEC 60332-1, IEC 60754-2, IEC 61034 

Technical data:

  • Electrical values Cat.7
  • Conductor AWG 23/1
  • Conductor diameter 1.4 mm
  • Cable diameter 18.0 mm
  • Weight 330 kg/km
  • Cable sheath FR-LSZH
  • Jacket color Aqua, RAL 6027
  • Transmission length Class EA ≤ 90 m
  • Fire load 3,120 MJ/km; 0.87 kWh/m
  • Temperature range -20°C to +60°C
  • Max. pull-in force 840 N
  • Permissible bending radius ≥ 100 mm (at rest), ≥ 200 mm (during pull-in)

Datasheet as PDF Download

Download (AWG23 B2ca)

Download (AWG23 Dca)

preLink® - System overview

Download

H.D.S. Indoor Cable Cat. 7 6x (4 x 2 x AWG 26) S/FTP Dca

H.D.S. Category 7 S/FTP indoor cable for easy cabinet-to-cabinet cabling in data centers and multi-connections from distribution rooms to sub-distribution rooms. The cable structure consists of 24 pair-shielded cable elements, with 4 pairs combined into one stranded element. Each stranded element is marked with a number band for easy identification. The flexible central strain relief element provides excellent protection for the cable during installation. The jacket is made of flexible LSOH material.

6 x (4 x 2 x AWG 26) S-FTP Dca

Application standards:

  • IEC 61156-5, ISO/IEC 11801 2nd ed.
  • EN 50173-5, EN 50288-4-2

Fire class:

  • Dca s2,d2,a1, EN 50575:2014 + A1:2016, IEC 60332-1, IEC 60754-2, IEC 61034

Technical data:

  • Electrical values Cat.7
  • Conductor AWG 26/1
  • Conductor diameter 1.0 mm
  • Cable diameter 13.9 mm
  • Weight 205 kg/km
  • Cable jacket FR-LSZH
  • Jacket color Aqua, RAL 6027
  • Transmission length Class EA ≤ 60 m
  • Fire load 2,171 MJ/km; 0.603 kWh/m
  • Temperature range -20°C to +60°C
  • Max. pull-in force 500N
  • Permissible bending radius ≥ 55mm (at rest), ≥ 110mm (during pull-in)