H.D.S. Indoor Cable
-
H.D.S. Indoor Cable Cat. 7, 6x (4 x 2 x AWG 23) S/FTP B2ca, S-FTP Dca
-
H.D.S. Category 7 S/FTP indoor cable for easy cabinet-to-cabinet cabling in data centers and multi-connections from distribution rooms to sub-distribution rooms. The cable structure consists of 24 pair-shielded cable elements, with 4 pairs combined into one stranded element. Each stranded element is marked with a number band for easy identification. The flexible central strain relief element provides excellent protection for the cable during installation. The jacket is made of flexible LSOH material.
6 x (4 x 2 x AWG 23) S-FTP B2ca
Application standards:
- IEC 61156-5, ISO/IEC 11801 2nd ed.
- EN 50173-5, EN 50288-4-2
Fire class:
- B2ca s1,d1,a1 acc. EN 50399, IEC 60332-1, IEC 60754-2, IEC 61034
Technical data:
- Electrical values Cat.7
- Conductor AWG 23/1
- Conductor diameter 1.4 mm
- Cable diameter 18.2 mm
- Weight 330 kg/km
- Cable sheath FR-LSZH
- Jacket color Aqua, RAL 6027
- Transmission length Class EA ≤ 90 m
- Fire load 3,120 MJ/km; 0.87 kWh/m
- Temperature range -20°C to +60°C
- Max. pull-in force 840 N
- Permissible bending radius ≥ 100 mm (at rest), ≥ 200 mm (during pull-in)
6 x (4 x 2 x AWG 23) S-FTP Dca
Application standards:
- IEC 61156-5, ISO/IEC 11801 2nd ed.
- EN 50173-5, EN 50288-4-2
Fire class:
- Dca s2,d2,a1 EN 50575:2014 + A1:2016, IEC 60332-1, IEC 60754-2, IEC 61034
Technical data:
- Electrical values Cat.7
- Conductor AWG 23/1
- Conductor diameter 1.4 mm
- Cable diameter 18.0 mm
- Weight 330 kg/km
- Cable sheath FR-LSZH
- Jacket color Aqua, RAL 6027
- Transmission length Class EA ≤ 90 m
- Fire load 3,120 MJ/km; 0.87 kWh/m
- Temperature range -20°C to +60°C
- Max. pull-in force 840 N
- Permissible bending radius ≥ 100 mm (at rest), ≥ 200 mm (during pull-in)
Datasheet as PDF Download
fixLink® - System overview
-
H.D.S. Indoor Cable Cat. 7, 6x (4 x 2 x AWG 26) S/FTP Dca
-
H.D.S. Category 7 S/FTP indoor cable for easy cabinet-to-cabinet cabling in data centers and multi-connections from distribution rooms to sub-distribution rooms. The cable structure consists of 24 pair-shielded cable elements, with 4 pairs combined into one stranded element. Each stranded element is marked with a number band for easy identification. The flexible central strain relief element provides excellent protection for the cable during installation. The jacket is made of flexible LSOH material.
6 x (4 x 2 x AWG 26) S-FTP Dca
Application standards:
- IEC 61156-5, ISO/IEC 11801 2nd ed.
- EN 50173-5, EN 50288-4-2
Fire class:
- Dca s2,d2,a1, EN 50575:2014 + A1:2016, IEC 60332-1, IEC 60754-2, IEC 61034
Technical data:
- Electrical values Cat.7
- Conductor AWG 26/1
- Conductor diameter 1.0 mm
- Cable diameter 13.9 mm
- Weight 205 kg/km
- Cable jacket FR-LSZH
- Jacket color Aqua, RAL 6027
- Transmission length Class EA ≤ 60 m
- Fire load 2,171 MJ/km; 0.603 kWh/m
- Temperature range -20°C to +60°C
- Max. pull-in force 500N
- Permissible bending radius ≥ 55mm (at rest), ≥ 110mm (during pull-in)
Datasheet as PDF Download